Complete Blackout and Brownout ProtectionAccording to Study by Bells Labs, under voltage sudden dips represent the majority of power problem. Wide Input range Online design of Uniline UPS prevent data loss caused by outrages brown outs.Computer Grade Line Conditioning with IsolationSuperior full time isolation is built into all Uniline UPS. Output is fully isolated by double conversion isolation transformer. No need to have extra isolationtransformer as required for Imported Systems. Remote Monitoring Control through SNMP / Internet also possible at extra cost. Optional. SALIENT FEATURES Wide Input Window Generator Compatible Computer Grade Power Superior Float Cum Boost Charger IGBT Based Hi - Frequency PWM Inverter O/P Distortion 3 Inverter Efficiency 92 High crest factor 4 1 Crystal controlled output frequency 50 Hz 0.01 Low noise 50 db upto 10 KVA Compact, sleek design Backup up to 8 Hrs RS 232 C / SNMP Inter.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 5 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 120 Minutes |
Minimum VAH | 16000 VAH |
Voltage Regulation From No Load To Full Load | 0.99 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 2 % |
Overall Efficiency | 95 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 38935 |
Type Test Certificate Date | 27.02.2014 |
Name Of Lab | UNILINE ENERGY SYSTEMS (PVT) LTD |
Address Of Lab | Uniline House, Ramesh Market, East of Kailash, New Delhi - 110 065, India |
Supply & Commissioning | Yes |
Warranty | 1 Years |