Sophisticated high specification on line configuration with static switch. State of the Art IGBT based pulse width modulation PWM technology to reduce harmonic distortion and increase both crest factor tolerance and dynamic stability. Higher efficiency of operation means UPS has significantly lower running costs than leading competitors. Continuously delivers full rated power at ambient as high as Parallel operation of UPS. Comprehensive indication of normal and fault conditions. Simple operating controls. Compatible with sealed maintenance free battery as well as tubular lead acid batteries. Compact cabinet ultra light weight. Easy installation with wheels for manoeuvreability and front bottom terminals. Optional remote status panel..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 20 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | Three phase 300 V - 450V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 150 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | Less than 2% with linear load % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | NA |
Type Test Certificate Date | NA |
Name Of Lab | NA |
Address Of Lab | NA |
Supply & Commissioning | NA |
Warranty | 1 Years |