1. Aska Water Mist CAF Fire Extinguisher Backpack type Low Pressure design with fire rating of 27A, 233B and 1000V using Standard AFFF Foam Compound. 2. V4A corrosion resistant special steel vessel grade 316, 3. The discharge gun has dual nozzle Jet and Spray, 4. Works on a pressure of below 15 bars., It has specially designed Gun placement holder and air cylinder mounting bracket, 5. Tested and Certified by CFEES DRDO New Delhi Centre for Fire Explosives and Environment Safety for all applicable Clauses as per EN 3-7 2004 A1 2007 and ERDA for non-conductivity as per IS 15683-2006 Cl. No. 8.6 EN 3-7 2004 A1 2007 E Cl. No. 9.
Other Specifications Download Specification | |
---|---|
Conformity To EN Standards | EN 3-7:2004+A1:2007 |
Cylinder Capacity | 4.7 Ltrs |
Mounting Type | Back pack |
Configuration (Shall Be Mounted On A Sturdy Frame Suitably Cushioned For Comfort, Provided With Shoulder Pads For Carrying As A Backpack And A Handle To Be Carried By Hand. All Materials Used Shall Be Of Fire Retardant Type. Backpack Shall Be Supplied With Two Air Cylinders.) | Yes |
Pressure | 8.5 Bar |
Fire Rating | 27 A, 233B, 1000V with Standard AFFF Compound conforming to UL-162 |
Type Of Foam | Standard Foam as per UL 162 or IS 4989 Standards |
If Special Foam Mention The Compostion For Special ,otherwise Put NA | NA |
Spreading Coefficient For Standard AFFF Compound Shall Be +3 Minimum | yes |
Spreading Coefficient For Special AFFF Compound Shall Be +5 Minimum | Yes |
Commercial Brand Name Of The Special Foam (fire Extinguishing Medium) As Per Accredited Laboratory Test Report Where In Fire Rating Has Been Achieved, To Be Declared. | NA |
The Concentration Of Compounds Shall Be Nominal 6% | Yes |
Extinguishing Medium | Water Mist & CAF |
Extinguishing Gun Material | Stainless Steel |
If Others Mentions The Material For Extinguishing Gun,otherwise Put NA | NA |
Extinguishing Gun Weight | 1670 grams |
Lancing Distance Of Gun | 14 meters |
Length Of EN Marked Hose | 1.3 meters |
Pressure Vessel Material | Stainless Steel |
Pressure Vessel Capacity | 9 Ltrs |
Compressed Air Cylinder Capacity At 300 Bar | 4.7 Ltrs |
Pressure Gauge To Monitor Air Cylinder Pressure | Yes |
Compressed Air Cylinder Material | Carbon composite |
The Air Hoses Shall Be Suitable For Minus 40 Deg C To 100 Deg C Temperatures | Yes |
Flow Rate ( Must Be In Range Of 0.42 To 0.45) | .42 ltr/sec |
Operating Time In Full Throttle ( Must Be In Range Of 20 To 23) | 21.7 seconds |
Weight Of Fully Charged System (#) | 23.5 kg |
Main Components: Pressure Vessel To Hold The Media With Safety Valve, Compressed Air Cylinder Couped With A Reducer, Hose Pipes For Discharge Of Water Mist Media, Extingushing Gun | yes |
System Shall Be Designed For Maximum Operating Temperature TSmax And Minimum Operating Temperature TSmin Of 60 Deg C Or More And 5 Deg C Or Less Respectively And Certified By The Manufacturer Accordingly | Yes |
"The Air Cylinders Shall Have PESO, Nagpur Approval " | Yes |
Test Certificate No. | CFEES/ATEG/WM/PMS/01 and HIMP/09/957 |
Test Report Date | 20.09.2010 and 13.09.2010 |
Name Of Lab Where Test Conducted | Centre for Fire Explosives and Environment Safety and ERDA |