Megger MPQ1000 Three Phase Power Quality Analyzer Hand Held with 3Nos current Clamps is an advanced 8 channel 3-phase Analyzer. It has key features like automatic CT recognition CTs are powered by the unit so there is no need for additional connections. Connection verification ensures the unit is configured correctly and you get the data you need. On-board data analysis saves time by allowing an immediate examination of data before leaving the site. Multiple communication methods USB, Ethernet, USB stick or32GB SD card allow for flexible and convenient operation.1000Vdc measurement allows testing and analysis of renewable applications dismissing the need for additional equipment. CATIV@600V assures a safe unit for all applications. IEC 61000-4-30 Class A compliant current ranges 60 A, 600A, 3000A and 6000A. For more info please refer datasheet of OEM. Warranty Three years on main instrument, one year on accessories. Price including GST@18percent.Delivery period 45days..
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Three phase |
Display Type | VGA Backlit |
Display Mode | Scope Mode and DVM Mode |
Number Of Current Channels | 4 Nos. |
Number Of Voltage Channels | 4 Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 0 to 1000V Volts Volts |
Measurable Voltage Accuracy | 0.1 Udin for 10 to 150 Udin |
Measurable Voltage Resolution | 16 Bit / .055V instantaneous reading Volts Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 0 to 6000A Ampere |
Measurable Current Accuracy | 1 of reading per IEC61000-4-30 +CT |
Measurable Current Resolution | 0.000165 x Ifs instantaneous reading Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 18MW total for 3 phases KW KW |
Power Accuracy | 1.75 U * I + CT affects max maximum error due to 1 phase error |
Power Resolution | 16 bit Watt Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 42.5 to 69.0 Hz Max harmonic freq.: 69 x 50 = 3450 Hz Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 0.05 x THD or 0.35 |
Resolution In Measurement Of Total Harmonics Distortion | 16 bit |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | 50 on MPQ 80 on PC |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | 0.0175 for PF |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | NA |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | NA |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | NA |
Measurable Crest Factor Accuracy | NA |
Measurable Crest Factor Resolution | NA |
Screen Memory | Yes |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | 32GB SD Card MB MB MB |
Type Of Battery Used | NiMH Battery pack |
Battery Backup | upto 8 Hours Hours Hours Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 1.82 Kg Grams Grams |
Dimensions(LXWXH) | 175x250x60mm cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | -20 to +50 degree celsius degree celsius degree celsius |
Operating Humidity | 0-95 % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | As per Data Sheet |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | CAT-IV 600V |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | R-2550P-2 |
TTC Report Date | 16 SEPTEMBER 2016 |
Name Of Lab | RT Laboratories |
Address Of Lab | Harleysvile USA |
Interface | USB/Ethernet |