Fluke 345 is more than an electric power meter. Combining the functions of a clamp meter, oscilloscope, data logger and digital power meter into one handy device, the Fluke 345 is ideal for working with variable frequency motor drives, high efficiency lighting and other loads using switching electronics.The internal memory of this electric power meter enables long-term power quality logging for analysis of trends or intermittent problems. Additionally, the Hall Effect clamp meter design makes measurement of dc current possible without the need to break the circuit.Setup and troubleshoot variable frequency drives and UPS systems,Harmonics measurements,Inrush capture,Load studies,AC/DC current,Highest safety rating,Accurate in noisy environments,Data logging,Verify batteries,Troubleshoot harmonics,Inrush current,Easy to use,3-Phase power,View graphs and generate reports, Warranty-01 Year, For Detailed specification please refer Fluke-345 Datasheet.
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Single phase |
Display Type | LCD Backlit |
Display Mode | 70 mm Diagonal |
Number Of Current Channels | 01 Nos. |
Number Of Voltage Channels | 01 Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 825 Volts |
Measurable Voltage Accuracy | V > 1 V: ± 1 % rdg ± 5 digits, V |
Measurable Voltage Resolution | 1 mV in 4 V range, 10 mV in 40 V range, 100 mV in 400 V range, 1 V in 750 V range Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 0 to 2000 A dc or 1400 ac rms Ampere |
Measurable Current Accuracy | I > 10 A: ± 1.5 % rdg ± 5 digits,I |
Measurable Current Resolution | 10 mA in 40 A range,100 mA in 400 A range,1 A in 2000 A range Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 0 to 1650 kW dc or 1200 kW ac KW |
Power Accuracy | 2.5 % rdg ± 5 digits, W1Ø |
Power Resolution | 1 VA in 4 kVA,10 VA in 40 kVA,100 VA in 400 kVA 1 kVA in 1200 kVA Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 15 Hz to 1 kHz Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | ± 3 % rdg ± 5 digits, ± 5 % rdg ± 5 digits |
Resolution In Measurement Of Total Harmonics Distortion | 0.1% |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | 30 |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | ± 3° |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | ± 3 % rdg ± 5 digits,± 5 % ± 2 digits,± 10 % ± 2 digits |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | 2 % ≤ RPL |
Facility To Measure Voltage And Current Unbalance | NA |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | 1.1 ≤ CF |
Measurable Crest Factor Accuracy | 1.1 ≤ CF |
Measurable Crest Factor Resolution | 0.01% |
Screen Memory | Available |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | Available MB |
Type Of Battery Used | Battery type 1.5 V Alkaline |
Battery Backup | > 10 hours (backlight on full), > 12 hours (backlight reduced) Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 820 Grams |
Dimensions(LXWXH) | 30.0 X 9.8 X 5.2 cmXcmXcm |
Provision For External SD Card | No |
Operating Temperature Range | 0 °C to 50 °C degree celsius |
Operating Humidity | 80 % for temperatures up to 31 °C (87 °F) decreasing linearly to 50 % relative humidity at 40 °C (104 °F) % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | 345 Power Quality Clamp Meter, Soft carrying case, Power Log software, Test leads, Alligator clips, Test probes, USB cable, International ac adapter / battery eliminator, Printed English language user manual, Multi-language manual CD |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | Safety IEC 61010-1 600 V CAT IV double or reinforced insulation, pollution degree 2 |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | STANDARD |
TTC Report Date | STANDARD |
Name Of Lab | STANDARD |
Address Of Lab | STANDARD |
Interface | USB |